DISC INSULATOR TOUNGUE & CLEVIS (T&C) TYPE

Applicable Standard IEC-61109
Power Frequency withstand voltage
Dry Min. 90 kVrms, Max. As per Requirement
Wet Min. 70kVrms, Max. As per Requirement
Lightning Impulse withstand voltage
Positive Min. 170 kVpeak, Max. As per Requirement
Negative Min. 170 kVpeak, Max. As per Requirement
Creepage Distance As per Requirement
Tensile Load 25kN, 40kN, 45kN, 70kN, 80kN, 90kN, 120kN
Fitting Designation (As per IEC-60120) 16/20